Your systems Engineer decided to assign Modbus discrete input numbers 100, 101 and 102 to the three switches and the other discrete inputs to 103 through 118.
CPU_BOOLEAN AppDITbl[16];
CPU_BOOLEAN AppSwStart;
CPU_BOOLEAN AppSwStop;
CPU_BOOLEAN AppSwReset;
CPU_BOOLEAN MB_DIRd (CPU_INT16U di, CPU_INT16U *perr)
{
*perr = MODBUS_ERR_NONE;
switch (di) {
case 100:
return (AppSwStart);
case 101:
return (AppSwStop);
case 102:
return (AppSwReset);
case 103:
case 104:
case 105:
case 106:
case 107:
case 108:
case 109:
case 110:
case 111:
case 112:
case 113:
case 114:
case 115:
case 116:
case 117:
case 118:
return (AppDITbl[di – 103]);
default:
*perr = MODBUS_ERR_RANGE;
return (FALSE);
}
}